Field Setting
(16) Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Setting Table
∗
(17) Setting of the Static Pressure Selection (for FXDQ model)
(18) External Static Pressure Settings (for FXMQ-P model)
The "SECOND CODE NO." is set to 07 (an external static pressure of 100 Pa) at factory setting.
*1 The FXMQ50 · 63 · 80 · 100 · 125· 140PVE cannot be set to 30 Pa.
*2 The FXMQ20 · 25 · 32 · 40PVE cannot be set to 180 or 200 Pa.
159
Mode No.
13 (23)
Some indoor unit models are not equipped with draft prevention (upward) function.
Model No.
13 (23)
MODE NO.
FIRST CODE NO.
13 (23)
First Code No.
Second Code No.
4
First Code No.
Second Code No.
5
SECOND CODE NO.
06
SiBE31-801_C
Setting
Upward (Draft
01
prevention)
02
Standard
Downward (Ceiling
03
soiling prevention)
External static pressure
01
Standard (15Pa)
02
High static pressure (44Pa)
External Static Pressure
01
30Pa (*1)
02
50Pa
03
60Pa
04
70Pa
05
80Pa
06
90Pa
07
100Pa
08
110Pa
09
120Pa
10
130Pa
11
140Pa
12
150Pa
13
160Pa
14
180Pa (*2)
15
200Pa (*2)
Test Operation