SiBE31-801_C
(13) Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to "01" at
the factory.
13 (23)
13 (23)
13 (23)
(14) Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory setting to "01."
Setting Table
(15) Operation of Downward Flow Flap: Yes/No
Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
Test Operation
In the Case of FXAQ, FXHQ
Mode No.
First Code No.
13(23)
0
In the Case of FXFQ25~80
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
In the Case of FXFQ100~125
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m
In the Case of FXUQ71~125
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.8 m
Mode No.
First Code No.
13 (23)
1
Mode No.
13 (23)
Second Code
No.
01
Wall mounted type: Standard
02
Wall mounted type: Slight increase
03
Wall mounted type: Normal increase
Setting
4-way Outlets
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
Setting
4-way Outlets
Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
Setting
4-way Outlets
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
Lower than 3.0 m Lower than 3.5 m Lower than 3.8 m
Second Code
No.
01
F : 4-direction airflow
02
T : 3-direction airflow
03
W : 2-direction airflow
First Code No.
Second Code No.
3
Setting
Ceiling height
3-way Outlets
2-way Outlets
Ceiling height
3-way Outlets
2-way Outlets
Ceiling height
3-way Outlets
2-way Outlets
Setting
Setting
01
Down-flow operation: Yes
02
Down-flow operation: No
Field Setting
158