Troubleshooting by Indication on the Remote Controller
C5
"
" Indoor Unit: Malfunction of Thermistor (R3T) for Gas
3.9
Pipes
C5
Remote
Controller
Display
Applicable
All indoor unit models
Models
Method of
Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction
Detection
Malfunction
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Supposed
Causes
Troubleshooting
∗
148
Defect of indoor unit thermistor (R3T) for gas pipe
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Remove the thermistor from
the indoor unit PC board, and
then insert it again.
Is the
thermistor normal?
NO
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
∗
5 kΩ to 90 kΩ
YES
Refer to "Thermistor Resistance / Temperature Characteristics" table on P.247.
YES
NO
SiBE28-805
Normal (The malfunction is
caused by faulty contact.)
Replace the thermistor (R3T).
Replace the indoor unit PC board.
Troubleshooting