3.10 " C5 " Indoor Unit; Malfunction Of Thermistor (R3T) For Gas Pipes; C5" Indoor Unit: Malfunction Of Thermistor (R3T) For Gas Pipes - Daikin VRV II RXYQ8MY1K Service Manual

R-410a heat pump 50/60hz for high outdoor temperature use
Table of Contents

Advertisement

Si39-502A

3.10 " C5 " Indoor Unit:

Pipes
C5
Remote
Controller
Display
Applicable
All indoor unit models
Models
Method of
Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction
Detection
Malfunction
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Supposed
Causes
Troubleshooting
∗ Refer to "Thermistor Resistance / Temperature Characteristics" table on P277.
Troubleshooting
Malfunction of Thermistor (R3T) for Gas
Defect of indoor unit thermistor (R3T) for gas pipe
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector is
connected to X11A of
the indoor unit PC
board.
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R3T) from the indoor
unit PC board.
(0.6kΩ~
360kΩ)
YES
Troubleshooting by Indication on the Remote Controller
NO
NO
Connect the connector and turn on
again.
Replace the thermistor (R3T).
Replace the indoor unit PC board.
(V2785)
163