A7" Indoor Unit: Malfunction Of Swing Flap Motor (Ma) - Daikin RXYQ5-48MAY1 Service Manual

R410a heat pump 50hz
Table of Contents

Advertisement

Si39-407
" A7 " Indoor Unit:
3.5
A7
Remote
Controller
Display
Applicable
FXCQ, FXHQ, FXKQ
Models
Method of
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Detection
Malfunction
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Decision
Conditions
Supposed
Causes
Troubleshooting
Malfunction of Swing Flap Motor (MA)
Defect of swing motor
Defect of connection cable (power supply and limit switch)
Defect of air flow direction adjusting flap-cam
Defect of indoor unit PC board
Troubleshooting by Indication on the Remote Controller
187