Controllable Integer Status (Inc) - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

SPA-ZC 402
SPA-ZC 402
11.2.2.18.
Table 11.2.2.18.-1 Controllable integer status (INC)
INC class
Attribute Name Attribute Type
DataName
Inherited from Data Class (refer to IEC 61850-7-2)
DataAttribute
ctlVal
CtxInt
operTm
TimeStamp
origin
Originator
ctlNum
INT8U
stVal
INT32
q
Quality
t
TimeStamp
stSeld
BOOLEAN
subEna
BOOLEAN
subVal
ValWithTrans
subQ
Quality
subID
VISIBLE
STRING64
persistent
BOOLEAN
ctlModel
ENUMERATED
sboTimeout
INT32U
sboClass
ENUMERATED
minVal
INT8
90
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
Different variants of the type exist based on the connectivity package
short address information (sAddr). Underlined information indicates
the basic type.

Controllable integer status (INC)

Table 11.2.2.18.-1 defines the common data class of controllable integer status.
FC
Control and Status
CO
CO
ST
ST
ST
ST
ST
ST
Substitution
SV
SV
SV
SV
Configuration, Description and Extension
CF
CF
CF
CF
CF
Value/ Value
TrgOp
range
0..255
dchg
qchg
dchg
Status-only |
direct-with-
normal-security |
sbo-with-normal-
security | direct-
with-enhanced-
security | sbo-
with-enhanced-
security
operate-once |
operate-many
1MRS755380
SPA-ZC 402/
M/O/C
Comments
Supported
AC_CO_M
Supported
AC_CO_O
Not Supported
AC_CO_O
Not Supported
AC_CO_O
Not Supported
M
Supported
M
Supported
M
Supported
AC_CO_O
Not Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
M
Not Supported
M
Supported
AC_CO_O
Not Supported
AC_CO_O
Not Supported
O
Not Supported

Advertisement

Table of Contents
loading

Table of Contents