ABB SPA-ZC 402 Installation And Commissioning Manual page 49

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

1MRS755380
Fig. 6.10.-2
Report Control Block
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
Buffered reporting needs mandatory Report Client definitions. Report Client
definitions link a certain RCB to a certain client. The client can import the CID file
to check which RCB instance it has to use. If the Max property is defined to 2, the
configuration must have two clients with buffered reporting. In the list, the client
who is defined first uses the first RCB instance (rcb name ...01) and the second RCB
uses second instance (rcb name ...02 ). It is not mandatory to define clients in
unbuffered reporting, but it is recommended for the sake of clarity. Client IED Name
has to match with the client name in Substation Configuration description Language
(SCL).
Every modification in the Dataset referenced in RCB increases the RCB
Configuration Revision property by one. The IEC 61850 client can verify the
deviations between the received configuration revision in the information report and
the imported configuration revision. If the configuration revisions do not match, the
client may discard the received information reports.
SPA-ZC 402
SPA-ZC 402
A040134B
49