ABB SPA-ZC 402 Installation And Commissioning Manual page 46

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

SPA-ZC 402
SPA-ZC 402
Fig. 6.9.-3
Data Object Instance Editor
46
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
13.Select the data object again and right-click to start the DOI Editor. The Data
Object Instance Editor window is shown, see Fig. 6.9.-3.
14.Define the properties and SPA variable definitions for each data object in the
Object Properties window. The stVal field in the DOI editor is automatically
updated with the data entered in the Object Properties.
Follow the same procedure for all data objects that you have added to the LN
object.
The SPA point data is written to the sAddr in the CID file for the selected data
object. SPA-ZC 402 uses this field to poll data and events from the IED.
In order to get automatic updating of the process objects, you should
add those data objects of interest to the dataset group. Refer to
Section 6.5. Using Dataset Editor.
1MRS755380