ABB SPA-ZC 402 Installation And Commissioning Manual page 89

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

1MRS755380
Table 11.2.2.17.-1 Controllable double point (DPC)
SPC class
Attribute Name Attribute Type
DataName
Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
ctlVal
BOOLEAN
operTm
TimeStamp
origin
Originator
ctlNum
INT8U
stVal
CODED ENUM
q
Quality
t
TimeStamp
stSeld
BOOLEAN
subEna
BOOLEAN
subVal
CODED ENUM
subQ
Quality
subID
VISIBLE
STRING64
pulseConfig
PulseConfig
ctlModel
ENUMERATED
sboTimeout
INT32U
sboClass
ENUMERATED
d
VISIBLE
STRING255
cdcNs
VISIBLE
STRING255
cdcName
VISIBLE
STRING255
dataNs
VISIBLE
STRING255
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
FC
Control and Status
CO
CO
ST
ST
ST
ST
ST
ST
Substitution
SV
SV
SV
SV
Configuration, Description and Extension
CF
CF
CF
CF
DC
EX
EX
EX
Value/ Value
TrgOp
range
off (FALSE) | on
(TRUE)
0..255
dchg
intermediate-
state | off | on |
bad-state
qchg
dchg
intermediate-
state | off | on |
bad-state
status-only |
direct-with-
normal-security |
sbo-with-normal-
security | direct-
with-enhanced-
security | sbo-
with-enhanced-
security
operate-once (0)
| operate-many
(1)
Text
SPA-ZC 402
SPA-ZC 402
SPA-ZC 402/
M/O/C
Comments
Supported
AC_CO_M
Supported
AC_CO_O
Not Supported
AC_CO_O
Supported
AC_CO_O
Supported
M
Supported
M
Supported
M
Supported
AC_CO_O
Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
AC_CO_O
Not Supported
M
Supported
AC_CO_O
Not Supported
AC_CO_O
Not Supported
O
Supported
AC_DLNDA_M Not Supported
AC_DLNDA_M Not Supported
AC_DLN_M
Not Supported
89