Scl Control Block; Protocol Implementation Conformance Statement; Profile Conformance - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

1MRS755380
Table 11.3.-3
Additional MMS services for SCL.2 and SCL.3
SCL conformance
MMS Services
GetCapability-
List
GetDomainAt-
tributes
LoadDomain
StoreDomain
a)
Must be m if support SCL.3 is declared.
b)
Must be m if support for remote creation of a SCL is declared.
11.4.
Table 11.4.-1
Definition of SCL control block
IEC 61850-8-
MMS
1Component
TypeDescription
Name
validate
VISIBLE-STRING
size of 64 octets
valState
Unsigned Integer -
8 bits
activate
VISIBLE-STRING
size of 64 octets
11.5.
11.5.1.
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
Client-CR
Base
F/S
O
i
O
o
a)
O
b)
O

SCL control block

The SCL control block must have a functional constraint of SC. This control block
must occur in LLN0 only.
The SCL control block must be a structured MMS type definition that contains the
ordered named components defined in Table 11.4.-1.
r/w
rw
r
rw

Protocol implementation conformance statement

In the following tables basic protocol conformance statements (PICS) are defined.

Profile conformance

Server-CR
Value/Range
Base
m/o
Comments
mo
Must be m if support for
remote activation of an SCL
is declared.
m
(0) - NOT-VALIDATED
(1) - VALIDATION-ERROR
(2) - VALIDATED
(3) - VALIDATION-IN-
PROGRESS
(4) - NOT-SUPPORTED
(5) - VALIDATE-FILE-
PRESENT
mo
Must be m if support for
remote activation of an SCL
is declared.
SPA-ZC 402
SPA-ZC 402
SPA-ZC 402/
F/S
Comments
Not Supported
o
i
Supported
o
m
Not Supported
a)
o
Not Supported
b)
o
Not Supported
SPA-ZC 402/Comments
N/A for TP client
N/A for TP client
N/A for TP client
101