Obtaining Error Logs - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

SPA-ZC 402
SPA-ZC 402
9.5.
66
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
Select Help > About to view the version information.
SPA-ZC 402 version information
*
The version information can be read from the device's label. If the device is
updated afterwards, use CET's IP query to get the correct version information
from the device memory. For more information about IP query, refer to
Section 9.3. IP Query.

Obtaining error logs

The following session transfers error.log file through ftp.
C:\>ftp x.x.x.x
User: abb
Password: abb
ftp> cd log
ftp> get error.log
ftp> quit
1MRS755380