Originator; Unit Definition - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

1MRS755380
11.2.1.6.
Table 11.2.1.6.-1
Step position with transient indication
OriginatorType Definition
Attribute Name
AttributeType
orCat
ENUMERATED
orIdent
OCTET STRING64
Table 11.2.1.6.-2
Values for orCat
Value
bay-control
station-control
remote-control
automatic-bay
automatic-station
automatic-remote
maintenance
process
11.2.1.7.
Table 11.2.1.7.-1
Unit
Unit Type Definition
Attribute Name
AttributeType
SIUnit
ENUMERATED
multiplier
ENUMERATED
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual

Originator

Value/ Value Range
not-supported | bay-
control | station-control |
remote-control |
automatic-bay |
automatic-station |
automatic-remote |
maintenance | process

Unit definition

Value/ Value Range
According to table in
Annex A
According to table in
Annex A
M/O/C
M
M
Explanation
Control operation issued from an operator using a client
located at bay level
Control operation issued from an operator using a client
located at station level
Control operation from a remote operater outside the
substation (e.g. network control center)
Control operation issued from an automatic function at bay
level
Control operation issued from an automatic function at station
level
Control operation issued from an automatic function outside of
the substation
Control operation issued from a maintenance / service tool
Status change occurred without control action (e.g. external
trip of a circuit breaker or failure inside the breaker)
M/O/C
M
O
SPA-ZC 402
SPA-ZC 402
SPA-ZC 402/
Comments
Supported
Supported
SPA-ZC 402/
Comments
Supported
Supported
73