General requirements

Table 8.2.-1
Environmental test and conditions
Recommended service temperature range
(continuous)
Limited temperature range (short-term)
Transport and storage temperature range -40...+70˚C according to the IEC 60068-2-48
Dry heat test
Dry cold test
Damp heat test, cyclic
Table 8.2.-2
Electromagnetic compatibility tests
EMC immunity test level meets the requirements listed below.
1 MHz burst disturbance test, class III According to the IEC 60255-22-1
Common mode
*
Differential mode
*
Electrostatic discharge test, class III
For contact discharge
*
For air discharge
*
Radio frequency interference tests
Conducted, common mode
*
Radiated, amplitude-modulated
*
Radiated, pulse-modulated
*
Fast transient disturbance tests
All terminals
*
Surge immunity test
Power supply, SPA-ZC402xxxA
*
Power supply, SPA-ZC402xxxC
*
RJ45-Cable
*
Power frequency (50 Hz) magnetic field
IEC 61000-4-8
Electromagnetic emission tests
Conducted, RF-emission (Mains
*
terminal)
Radiated RF-emission
CE approval
-10...+55˚C
-40...+85˚C
According to the IEC 60068-2-2
According to the IEC IEC 60068-2-1
According to the IEC 60068-2-30
2.5 kV
1.0 kV
According to the IEC 61000-4-2 and IEC 60255-22-
2
8 kV
Not applicable
According to the IEC 61000-4-6 and IEC 60255-22-
6 10 V (rms), f=150 kHz...80 MHz
According to the IEC 61000-4-3 and IEC 60255-22-
3 10 V/m (rms), f=80...2700 MHz
According to the ENV 50204 and IEC 60255-22-3
10 V/m, f=900 MHz
According to the IEC 60255-22-4 and IEC 61000-4-
4
4 kV
According to the IEC 60255-22-5 and IEC 61000-4-
5
4 kV line-to-earth, 2 kV line-to-line
2 kV line-to-earth, 1 kV line-to-line
2 kV line-to-earth
300 A/m continuous
According to the EN 55011
EN 55011, class A, IEC 60255-25
EN 55011, class A, IEC 60255-25
Complies with the EMC directive 2004/108/EC and
the LV directive 2006/95/EC