Hitachi FSG1 Series Technical Catalogue page 388

Set-free outdoor and indoor units
Table of Contents

Advertisement

17
TEST RUN
/12
n
Remarks:
In case of cooling operation, the curves of "Expansion Valve
Opening" for indoor unit is not available due to the following
reasons.
a) The range of indoor unit valve opening for stability is wide
due to balancing control (*3) even if Td · SH is the same.
b) Indoor Units Expansion Valve Opening is slightly
changed depending on the total indoor unit quantity and
capacity to be connected.
c) Indoor Unit Expansion Valve Opening slightly changed
depending on the piping length.
Outdoor Unit Model (Serial No.
(1)
Operation Mode
(2)
Test Run Start Time
(3)
Data Collect Start Time
(4)
Read Out Data from 7-Segment in Outdoor Unit
Protection Control Code
Outdoor Microcomputer Output
Indoor Total Operating Capacity
Inverter Frequency
Compressor Running Quantity
Air Flow Ratio
Outdoor Unit Expansion Valve Opening
Discharge Pressure
Suction Pressure
Discharge Gas Temperature
Heat Exchanger Liquid Pipe Temperature
Outdoor Temperature
Compressor Running Current
Indoor Unit
Expansion Valve Opening
Heat Exchanger Liquid Temp
Heat Exchanger Gas Temp
Intake Air Temp
Outlet Air Temp
Capacity (X 1/8HP)
Indoor Unit Stoppage Cause Code
Restricted Control for Prevention of
Compression Ratio Decrease
Restricted Control for Prevention of
High Pressure Increase
Restricted Control for Prevention of
Discharge Gas Temp. Increase
Restricted Control for Prevention of
TdSH Decrease
Restricted Control for Prevention of
Overcurrent
Accumulated Operation Time of Comp. 1
Accumulated Operation Time of Comp. 2
Accumulated Operation Time of Comp. 3
Accumulated Operation Time of Comp. 4
Outdoor Alarm Code
Inverter Stoppage Cause Code
Total Indoor Unit Capacity (X 1/8HP)
Total Indoor Unit Quantity
Refrigerant System Address
)
RAS-
52C
52C
1
SC
FAN
RS
2
oP
H1
CC
Fo
oE1
oE2
oEb
Pd
Ps
Td1
Td2
Td3
Td4
TE1
TE2
To
A1
A2
A3
A4
iE
TL
TG
Ti
To
CA
d1
c11
c13
c15
c16
c17
UJ1
UJ2
UJ3
UJ4
AC
iTC
CP
AA
GA
d) In the case that the additional refrigerant charge is
required, the correct quantity of refrigerant to be charged
should be calculated, measured and charged.
?
NOTE:
(*3) Balancing Control
Depending on the operating conditions of indoor units,
the expansion valve opening of each indoor units is
adjusted to keep the balance of refrigerant flow in the
cycle.
(Serial No.
)
RAS-
52C
52C
AC Chopper
52C
2
3
4
20A
21
21
OH
FAN
1
2
(Serial No.
)
52C
52C
52C
AC Chopper
1
2
3
4
RS
20A
21
21
OH
2
1
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fsg seriesFxg seriesFxg1 series

Table of Contents