UNITS INSTALLATION
12
/24
12.8.4 MULTIPLE INSTALLATION SPACE
I
In case of RAS 5/8/10 HP
Keep the upper side open to prevent air short-circuiting.
§ In case that the front and either of the sides are open.
- Installation in the same direction
Provide a distance of min. 1000 mm to the next unit.
- Refer to rear Installation
Provide a distance of min. 1000 mm to the next unit.
§ In case that the surrounding wall exists.
- Installation in the same direction
No limit to wall height
No Limit to wall Height
No limit to wall height
* A space of 900mm is recommended for easier service work.
(Front)
(Front)
(Max. 3 Units in a Row)