General Data For Indoor Units; General Data; Rci - 4-Way-Cassette Type - Hitachi FSG1 Series Technical Catalogue

Set-free outdoor and indoor units
Table of Contents

Advertisement

GENERAL DATA

2
/2

2.1. GENERAL DATA FOR INDOOR UNITS

2.1.1.

RCI - 4-WAY-CASSETTE TYPE

MODEL RCI
Nominal Cooling Capacity
Nominal Heating Capacity
Air Flow Rate (Hi/Me/Lo)
Fan Motor
Sound Pressure Level
(Overall A Scale)
Height
Outer Dimensions
Width
Depth
Net Weight
Refrigerant
Connections
Refrigerant Piping
Liquid Line
Gas Line
Condensate Drain
Packing Measurements
Standard accessories
Adaptable Air Panel Model
Color (Munsell Code)
Height
Outer Dimensions
Width
Depth
Net Weight
Packing Measurements
Optional Accessories
?
NOTE:
1. The nominal cooling and heating capacity is the
combined capacity of the HITACHI standard split
system, and are based on the JIS 158616.
Operation Conditions
Indoor Air Inlet Temperature
Outdoor Air Inlet Temperature
Piping Length: 7.5 meters; Piping Lift: 0 meter
DB: Dry Bulb; WB: Wet Bulb
Units
RCI-1.0
RCI-1.5
W
2 800
4 300
W
3 300
4 900
3
m
/min
8/7/6
13/11/10
W
12
dB (A)
35/33/30
38/35/32
mm
298
mm
820
mm
820
kg
30
R407C (Nitrogen Charged in Factory for Corrosion-Resistance)
mm (in.)
6.35(1/4)
6.35(1/4)
mm (in.)
12.7(1/2)
12.7(1/2)
Æ32 OD
Æ32 OD
mm
3
m
0.30
0.30
-
Standard
P-G12WA2E
With Wireless
P-G12WAH2E
With Heater
With Wireless
& Heater
mm
31+10
31+10
mm
950
mm
950
kg
7
3
m
0.12
0.12
-
Cooling
Heating
20.0 °C
DB
27.0 °C
WB
19.0 °C
7.0 °C
DB
35.0 °C
6.0 °C
WB
RCI-2.0
RCI-2.5
5 600
7 100
6 500
8 100
15/13/10
18/15/12
23
30
30
38/36/32
40/37/33
298
298
298
820
820
820
820
820
820
30
32
34
Flare-nut Connection (With Flare-Nuts)
6.35 (1/4)
9.53 (3/8)
15.88 (5/8)
15.88 (5/8)
Æ32 OD
Æ32 OD
0.30
0.30
Suspension Brackets
P-G23WA2E
P-G23WAH2E
P-G23WA2E1
P-G23WAH2E1
Spring White (4.1Y 8.5 / 0.7)
31+10
31+10
950
950
950
950
950
950
7
7
7
0.12
0.12
Remote Control Switch (PC-P1HE or PC-2H2)
2. The Sound Pressure Level is based on the following
conditions:
– 1.5 meters beneath the Unit
– Voltage of the power source for the indoor fan motor
is 220V.
The above data was measured in an anechoic chamber
so that reflected sound should be taken into
consideration when installing the unit.
3. For more information about capacities, see chapter 4.
4. Panels P-G12WAH2E, P-G23WAH2E(1) and
P-G46WAH2E(1), are equipped with wireless receiver
kit.
5. All the panels P-G12WA(H)2E, P-G23WA(H)2E1 and
P-G46WA(H)2E1, have been equiped with dew
prevention Heater.
RCI-3.0
RCI-4.0
RCI-5.0
8 400
11 200
14 200
9 600
13 000
16 300
21/18/15
32/28/24
34/29/25
30
60
41/39/33
45/41/37
46/41/37
298
348
348
820
1140
1 140
820
820
820
34
43
9.53 (3/8)
9.53 (3/8)
9.53 (3/8)
15.88 (5/8)
19.05 (3/4)
19.05 (3/4)
Æ32 OD
Æ32 OD
Æ32 OD
0.30
0.45
0.45
P-G46WA2E
P-G46WAH2E
P-G46WA2E1
P-G46WAH2E1
31+10
31+10
31+10
950
1270
1270
950
950
950
7
10
0.12
0.22
0.22
OD: Outer Diameter
60
44
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fsg seriesFxg seriesFxg1 series