4.8. CORRECTION FACTOR FOR DEFROSTING OPERATION
The heating capacity, excludes the defrosting operation period.
When considering defrosting operation, the heating capacity should be corrected by the factor below.
Corrected Heating Capacity = Correction Factor x Heating Capacity
Outdoor Inlet Air Temp. (ºC DB)
(Humidity=85% RH)
Correction Factor 5 ~ 20 FSG
Correction Factor 24 / 30 FSG1
Correction Factor 8 / 10 FXG
Correction Factor 20 / 30 FXG1
?
NOTE:
The correction factor is not valid for special conditions
such as snowfall or operation in a transitional period.
Heating
Capacity
4.9. FAN PERFORMANCE
Air flow (m³/min)
-7
-5
0.96
0.94
0.95
0.93
Reduced Capacity
due to frost build up.
1 Cycle
RPI-0.8-1.0
CAPACITIES AND SELECTION DATA
-3
0
3
0.90
0.89
0.90
0.88
0.85
0.87
Time
Defrosting max. 10 min.
RPI-1.5
Air flow (m³/min)
4
/17
5
7
0.92
1.0
0.90
1.0