Ras - Outdoors Unit (Fxg/Fxg1) - Hitachi FSG1 Series Technical Catalogue

Set-free outdoor and indoor units
Table of Contents

Advertisement

GENERAL DATA
2
/10
2.2.2.

RAS - OUTDOORS UNIT (FXG/FXG1)

Model
Power Supply
Nominal Cooling
Nominal Heating Capacity
Cabinet
Color (Munsell Code)
Sound Pressure Level
(Overall A Scale)
Outer Dimensions
Height
Width
Depth
Net Weight
Refrigerant
Flow Control
Compressor
Model
Quantity
Motor Output (Pole)
Oil quantity
Heat Exchanger
Condenser Fan
Quantity
Air Flow Rate
Motor Output (Pole)
Refrigerant Piping
Liquid Line
Gas Line
Low
Pressure
High
Pressure
Refrigerant Charge
Wiring Holes
Power Supply
Control Circuit
Connecting Wire between
Indoor and Outdoor Unit
Approximate
Packing Measurement
?
NOTE:
1. The Sound Pressure Level is based on following
conditions:
- 1 meter from the unit front surface and 1.5 meter
from floor level.
The above data was measured in an anechoic
chamber so that reflected sound should be taken
into consideration in the field.
RAS-8FXG
kW
22.6
kW
26.1
Synthetic Resin Paint Baked on Galvanized Steel Plate
dB
51
mm
1 645
mm
950
mm
750
kg
295
G402DHVM+
G401DHM
1+1
kW
3.0+3.0 (2)
l
7.0
1
m³/min
138
W
275(6)
Flare-Nut and/or Flange Connection (Factory supplied)
mm
Ø12.7
(in.)
(1/2)
mm
Ø25.4 or Ø22.2
(in.)
(1 or 7/8)
mm
Ø19.05
(in.)
(3/4)
kg
15.5
mm
Ø56
mm
Ø26.5
2
1.46
RAS-10FXG
RAS-20FXG1
AC 3B B B B , 380-415V, 50Hz
28.3
56.0
32.6
63.0
Beige (2.5Y 8/2)
53
62-57 (Night Shift)
1 645
1 645
950
1910
750
750
300
565
R407C
Micro-Computer Control Expansion Valve
Hermetic (Scroll)
G402DHVM+
G404DHD+
G501DHM
G603DH+
G1200EH
1+1
3.0+3.75 (2)
3.0(4)x1
+7.5(2)+4.4(2)
7.0
12.7
Multi-Pass Cross-Finned Tube
Propeller Fan
1
172
344
275(6)
275(6)x2
Ø12.7
Ø15.88
(1/2)
(3/4)
Ø28.6
Ø34,92 or Ø38.1
(1-1/8)
(1-3/8 or 1-1/2)
Ø19.05
Ø22.2 or Ø25.4
(3/4)
(7/8 or 1)
17.0
22.0
Ø56
Ø56
Ø26.5
Ø26.5
2
1.46
2.85
Conditions: as designed in Eurovent procedures for
sound testing.
In case of Night Shift conditions, the noise level
decrease 2 dB (A)
2. The outdoor unit is charged with refrigerant before
shipment. The charged volume is the equivalent of
a refrigerant piping of 10 meters, when combining
to HITACHI standard indoor unit.
RAS-30FXG1
85.0
95.0
64-59 (Night Shift)
1 645
2 870
750
855
G404DHD+
G603DH+
G1200EHx2
3
4
3.0(4)x1+4.4(2)x1
+7.5(2)x2
14.2
2
3
531
275(6)x3
Ø22.2
(7/8)
Ø41.3 or Ø44.5
(1-5/8) or 1-3/4)
Ø28.6 or Ø31.75
(1-1/8 or 1-1/4)
26.0
Ø70
Ø26.5
2
2
4.32