9.2.2.

PRINTED CIRCUIT BOARD LAYOUT (ONLY RPK)

n
PCB drawing
The PCB in the Indoor Unit is operating with 5 types of
DIP Switches, 1 sliding Switch, 1 Rotary Switch and 1
push Switch. The location is as follows:
CONNECTOR INDICATION
PCN1
Transformer 220V
PCN7
Power Source (1-R, 3-S)
THM1
Inlet Air
THM2
Air Outlet
THM3
Liquid Pipe
THM5
Gas Pipe
CN1
Transformer (pin 1-2: 17.3V / pin 3-4: 20.8V
CN2
Control Circuit for Outdoor Unit H-Link
CN3
Input Optional Functions
CN4
Input Optional Functions
CN7
Output Optional Functions
CN8
Output Optional Functions
CN11
Expansion Valve Control
CN13
Remote control SW (PC-P1HE)
CN17
Swing Louver Motor 1
CONTROL SYSTEM
LED's INDICATION
LED1
Red
LED3 Yellow
LED4
Red
CONNECTOR INDICATION
CN22
Swing Louver Motor 2
CN25
PCB2 wireless Receiver Part connection
CN26
PCB1 (P) Connection
CN27
Not used
CN28
PCB1 (M) Connection
CN29
Fan Motor
CN201
PCB1 Wireless Receiver Part Connection
CN303
Not Used
HA
Not Used
PSW301
Switch for emergency operation
DSW2
Optional Functions
DSW3
Capacity Code
DSW5
Ref. Cycle Nº
DSW6
Model Code
DSW7
Fuse Recover
RSW
Setting of indoor unit number
9
/7
This LED indicates the
transmission state between
Indoor Unit and RCS
This LED indicates the
transmission state between
the indoor unit and outdoor
unit
Power Source for PCB