REFRIGERANT PIPING AND REFRIGERANT CHARGE
13
/24
13.4. INDOOR UNIT PIPING WORK CONNECTION
13.4.1. RCI – 4 WAY CASSETTE TYPE
Position of piping connection is the following, which is
available from all directions, top, left or right.
Piping size
¡ ¡ ¡ ¡
Gas Piping
RCI-1.0/1.5
Ø 12.7 (1/2)
RCI-2.0
Ø 15.88 (5/8)
RCI-2.5/3.0
RCI-4.0/5.0
Ø 19.05 (3/4)
13.4.2. RCD – 2 WAY CASSETTE TYPE
Piping size
¡ ¡ ¡ ¡
Gas Piping
RCD-1.0/1.5
Ø 12.7 (1/2)
RCD-2.0
Ø 15.88 (5/8)
RCD-2.5/3.0
RCD-4.0/5.0
Ø 19.05 (3/4)
13.4.3. RPC – CEILING TYPE
n
¢ ¢ ¢ ¢
Liquid Piping
Ø 6.35 (1/4)
Piping size
Æ 9.53 (3/8)
RPC-2.0
RPC-2.5/3.0
RPC-4.0/5.0
n
¢ ¢ ¢ ¢
Liquid Piping
Ø 6.35 (1/4)
Æ 9.53 (3/8)
Piping Position
The refrigerant piping can be connected to some one of
two directions of the indoor unit: upper or rear side, when
facing the unit.
– The positions of piping are shown below
– Each direction has the prepared knockout hole as
shown in piping work sub-chapter.
– Cut the knockout hole for the required direction.
Liquid piping
Gas Piping
Gas Piping
Æ 15,88 (5/8)
Æ 19.05 (3/4)
Piping Work Installation
Piping work should be performed from the bottom side of
the unit. Remove the air inlet grille before beginning the
piping work, according to the following steps:
1. Slide the Knobs to the rear side.
Slide
Knob
2. Open the air inlet grille, push up and slide the air inlet
grilles to the rear side.
Unit
Open
Air Inlet Grille
Drain Piping
Liquid Piping
Æ 6.35 (1/4)
Æ 9.53 (3/8)
Rear Side
Push