Electrical Wiring - Hitachi FSG1 Series Technical Catalogue

Set-free outdoor and indoor units
Table of Contents

Advertisement

INSTALLATION OF OPTIONAL REMOTE CONTROLLER
16
/20
3. Attach the holding bracket onto the switch box

16.4.4 ELECTRICAL WIRING

Use this Timer with Remote Control Switch or Central
Station.
&
CAUTION:
Use the twist pair cable (1P-0.75mm²) as a
transmitting wire cable for prevention of the
malfunction.
Keep a distance more than 30cm between the remote
control cable and the transmission wire of Indoor units
3. In case of using Timer PSC-5SE (Central Station):
PSC-5T
Connector
Accessory Cable (1m)
To other central
Twist Pair Cable 1P-
Stations
0.75mm² (Max.
1000m)
Fix the holding
bracket with the
mark " ­ UP"
upward
Screw
(Accesory)
Up to 8 units of central Station (PSC-5S) and Timer (PSC-5T) can be connected to the H-LINK system.
PSC-5SE
One Timer control one Central Station and plural central Stations can not be controlled by one Timer
Power Supply:
AC220V or 240V
Available for H-LINK
connection (to be
connected to the terminal
boards 1 and 2 of Indoor
unit or Outdoor unit
1. In case of using timer with PC-P1HE:
Transmission Wire
between Outdoor Unit
and indoor Unit (H-LINK)
Indoor Unit
PSC-5T
PC-P1H
Twist Pair cable 1P-0.75mm²
(Max. 100m) Field-Supplied
2. In case of Using Timer with PC-2H2:
Transmission Wire
between Outdoor Unit
and indoor Unit (H-LINK)
Indoor Unit
PSC-5T
PC-2H2
Connector
TIMER REMOCON
(white)
Accessory Cable (1m)
CN13
(yellow)