General data

1 GENERAL DATA
Hardware Specifications
Item
Power supply
Consumption
Outer dimensions
Weight
Assembling conditions
Ambient temperature
Humidity
MODBUS
Item
Type
K5
Communication line
Communicatrion system
Communication method
Baud rate transmission
Length
H-LINK
Item
Communication with
Communication line
Communications system
Communication method
Speed of transmission
Length of wiring
Maximum number of gateways
Maximum number of chillers
N O T E
• Check chapter Electrical wiring for wiring details.
• This manual provides basic information for installing and wiring CHL-MBS-01.
• RCME-AH chillers use a different H-Link protocol compared with AG(1) and AG2(B) chillers, so they cannot be connected on to the
same H-Link line when using the same CHL-MBS-01.
7
PMML0301A rev.0 - 09/2013
Specifications
1~ 230 V ±10% 50Hz
25 W (maximum)
Width: 119 mm, Depth: 272 mm, Height: 46 mm
1.75 kg
Indoors (in a control panel or desktop)
0~40 °C
20~85% (Without condensation)
Specifications
Modbus RTU
Serial Port RS485 (3 Pins connector) - MODBUS Protocol
Twisted pair cable. Polarity
Half-duplex, multipoint serial connection
Non parity or odd/even parity selection. Data lenght: 8 bits - 1 stop bit
19200/9600 Baud
max. 1200 m according EIA-485
Specifications
HITACHI CHILLER
Twisted pair shielded cable, non polarity
Half-duplex
Asynchronous
9600 Bauds
1000 m maximum (total length of HLINK I/O bus)
1 CHL-MBS-01/H-LINK SYSTEM (CHILLER)
1 x CHL-MBS-01 can control up to 8 RCME-AH chillers (8 chillers x 8 modules  64 modules)
1 x CHL-MBS-01 can control up to 8 x AG(1), AG2(2)(B), WG(2), CLG(2) chillers (*AG2(2) chiller models >
3 cycles are counted as 2 chillers)