Stand-Alone Units; Cooling - Omron SX-F Instruction Manual

High power direct torque control inverters
Table of Contents

Advertisement

Stand-alone units

2-2
Stand-alone units
2-2-1

Cooling

Table 4
Mounting and cooling
SX-F, side-by-side
(mm)
SX-F wall, wall-one side
(mm)
16
The VSD must be mounted in a vertical position against a flat surface. Use the
template (delivered together with the VSD) to mark out the position of the fix-
ing holes.
Fig. 6 Mounting models 4090-4800 and 6090-61K0
Fig. 6 shows the minimum free space required around the VSD for the models
40P7-4800 and 6090-61K0 in order to guarantee adequate cooling. Because
the fans blow the air from the bottom to the top it is advisable not to position
an air inlet immediately above an air outlet.
The following minimum separation between two variable speed drives, or a
VSD and a non-dissipating wall must be maintained. Valid if free space on
opposite side.
a
b
c
d
a
b
c
d
Note When a 4160-4800 or 6315-61K0 model is placed between two walls, a
minimum distance at each side of 200 mm must be maintained.
40P7-47P5
4011-4037
200
200
200
200
0
0
0
0
100
100
100
100
0
0
0
0
Section 2-2
4160-4800
4045-4132
6315-61K0
6090-6250
cabinet
200
100
200
0
0
0
0
0
100
100
100
0
0
0
0
0