Function Blocks/ITEMs Incompatible with Earlier Versions

1-5
Function Blocks/ITEMs Incompatible with Earlier Versions

1-5-1 Incompatibility with Versions Earlier than Version 1.20

1-5-2 Incompatibility with Versions Earlier than Version 1.50
The following function blocks can be used only when Loop Control Unit
CS1W-LC001 Ver.1.20 and onwards and CX-Process Tool Ver.1.20 and on-
wards are used:
• The following function blocks can be registered on CX-Process Tool when
Loop Control Unit Ver.1.0j and CX-Process Tool Ver1.20 or onwards are
used. If the data of these function blocks is downloaded to the Loop Control
Unit by LCU element when these function blocks are registered on CX-Pro-
cess Tool, however, an error occurs, and the download is canceled. (Other
function blocks also are not downloaded.)
• The following function blocks cannot be registered on CX-Process Tool when
Loop Control Unit Ver.1.20 and onwards and CX-Process Tool Ver.1.00 are
used. For this reason, these function blocks cannot also be downloaded to the
Loop Control Unit. If the following function blocks already exist on the Loop
Control Unit and are uploaded to CX-Process Tool, only the following function
blocks are not uploaded. (When a new upload is performed, these blocks be-
come empty.)
2-position ON/OFF (Block Model 001), 3-position ON/OFF (Block Model
002), Blended PID (Block Model 013), 3-input Selector (Block Model
163), 3-output Selector (Block Model 164), Batch Data Collector (Block
Model 174), DI Terminal from Expanded CPU Unit (Block Model 455),
DO Terminal from Expanded CPU Unit (Block Model 456), AI Terminal
from Expanded CPU Unit (Block Model 457), AO Terminal from Expand-
ed CPU Unit (Block Model 458)
Note The version of the Loop Control Unit can be verified in the Monitor Run Status
Screen (Execution, Operation, Monitor run status) on CX-Process Tool.
When the above function blocks are used, check in the Check System Operation
screen on CX-Process Tool beforehand that the content of ITEM 099 onwards in
the System Common block (Block Model 000) is as follows:
ITEM
099
The following function blocks described in this manual can be used only when
Loop Control Unit CS1W-LC001 Ver.1.50 and onwards and CX-Process Tool
Ver.1.50 and onwards are used:
• The following function blocks can be registered on CX-Process Tool when ver-
sions of Loop Control Unit earlier than Ver.1.50 (Ver.1.0j or Ver.1.20) and CX-
Process Tool Ver1.50 or onwards are used. However, if the data of these func-
tion blocks is downloaded to the Loop Control Unit by LCU element (data for
one Loop Control Unit) when these function blocks are registered on CX-Pro-
cess Tool, an error occurs, and only those function blocks are not downloaded.
(Other function blocks are downloaded successfully.)
• The following function blocks cannot be registered on CX-Process Tool when
Loop Control Unit Ver.1.50 and onwards and versions of CX-Process Tool low-
er than Ver.1.50 (Ver.1.00 or Ver. 1.20) are used. For this reason, these func-
tion blocks cannot also be downloaded to the Loop Control Unit.
If the following function blocks already exist on the Loop Control Unit and are
Data name
MPU/FROM version indication V1.20
Version V1.20 and onwards must be indicated.