Error Codes
Error code
Fins-
CX-
Gateway
Server
ERROR
ERROR
An attempt has been made to
CODE:
CODE:
register more than 4,000 step
(110C)
(0A0D)
ladder sequence instructions for
one Loop Controller.
Even though ITEM 059 in the
LCBjj's System Common
block (block model 000) is set to
0 to enable using the HMI, the
EM Area bank specified in ITEM
050 (EM Area bank to allocate to
HMI) cannot be used because
the specified bank does not exist
in the CPU Unit or the specified
bank has been converted to file
memory.
An attempt has been made to
write an ITEM that cannot be
written while the operation of the
CX-Process Tool is suspended.
A cold start or hot start was
attempted during backup
processing.
ERROR
ERROR
A destination address is not set
CODE:
CODE:
in the FinsGateway routing
(0501)
(0501)
tables.
ERROR
ERROR
There are no backup files in the
CODE:
CODE:
Memory Card.
(2006)
(2006)
ERROR
ERROR
The backup data in the Memory
CODE:
CODE:
Card is set to read-only.
(2101)
(2101)
ERROR
ERROR
The number of files in the
CODE:
CODE:
Memory Card has reached the
(2103)
(2103)
limit.
ERROR
ERROR
There are no backup files in the
CODE:
CODE:
Memory Card.
(2106)
(2106)
ERROR
ERROR
(LCB05D only) The backup, clear
CODE:
CODE:
all, recovery, or download
(2102)
(0A16)
operation was attempted during
CPU Unit duplex initialization
processing.
ERROR
ERROR
There is no Memory Card
CODE:
CODE:
inserted.
(2301)
(2301)
ERROR
ERROR
The data in the Memory Card is
CODE:
CODE:
corrupted.
(250F)
(250F)
ERROR
ERROR
The Memory Card cannot be
CODE:
CODE:
accessed.
(3001)
(3001)
Backup during operation was
started when data was being
transferred.
ERROR
ERROR
Built-in flash memory is being
CODE:
CODE:
initialized.
(2108)
(2108)
320
Probable cause
Probable cause
Possible remedy
Possible remedy
A maximum of 4,000 step ladder sequence instructions
can be registered for each Loop Controller.
Correct the setting of ITEM 050 (EM Area bank to allocate
to HMI) in the LCBjj's System Common block (block
model 000).
Not all ITEMs can be written while operation is suspended.
Execute the cold start after the backup has been
completed.
Correct the routing tables.
There are no backup files in the Memory Card. Insert a
Memory Card containing backup files.
Set the backup data in the Memory Card to read/write. The
path name of the files is as follows:
<memory_card>\LCBDATA\CFBackUp.dat
Delete files from the Memory Card.
There are old backup files in the Memory Card in the
active CPU Unit when duplex Memory Card operation is
being used for Duplex Process-control CPU Units
(CS1D-CPU6jP). Delete the old backup files from the
Memory Card.
A backup, clear all, recover, or download cannot be
performed during CPU Unit duplex initialization processing.
Perform the backup, clear all, recovery, or download after
the CPU Unit duplex initialization processing has been
completed.
Insert the Memory Card properly.
When using duplex Memory Card operation for Duplex
Process-control CPU Units (CS1D-CPU6jP), place the
same backup files in the Memory Cards for both the active
and standby CPU Units.
Either the backup data in the Memory Card is corrupted or
the Memory Card is damaged. Create the backup files
again or use a new Memory Card.
Another application is accessing the Memory Card. Wait
for the Memory Card to be released and then try again.
Transfer the data again after the backup operation has
been completed.
Built-in flash memory is being initialized. Wait for a little
while for the initialization of built-in flash memory to be
completed and then try transferring the data again.
If you still cannot transfer the data, the hardware may be
damaged. Contact your OMRON representative.