Tuning
MV Adjustment Area
Details
MV open direction
enabled (0%)
AUTO or
remote (CAS)
No Manual Pointer
2-position ON/OFF (001)
AUTO or remote (CAS)
Remote/Local (R/L) Switching
When the SP setting (local only, or remote/local both possible) for ITEM024 for
Basic PID, Advanced PID, Indication and Setting, Ratio Setting, 2-position ON/
OFF, and 3-position ON/OFF is 1 (remote/local both possible), CAS is displayed.
When the CAS Button is red, the setting is on remote SP. When the CAS Button
is blue, the setting is on local SP. Click the CAS Button to switch the setting.
Note When the CX-Process Monitor is set to Remote SP, A/M automatically switches
to AUTO. You cannot set Manual.
A/M Switching
When AUTO is lit red, the setting is AUTO. You can change the SP value. When
MAN is lit blue, the setting is manual. You can change MV and SP values. Select
AUTO or MAN to switch.
The MV Adjustment Area is displayed for the following function blocks:
Basic PID (011), Advanced PID (012), Batch Flowrate Capture (014), Indication
and Operation (032), and Ratio Setting (033)
MV open direction
enabled (100%)
Manual
Manual
Pointer
Make Manual Pointer and MV open direction settings when registering the Con-
trol Screen.
Make output limit (ML, MH) settings using the Tuning Screen.
AUTO or MAN
Output operation switches
AUTO or
remote (CAS)
Output limit (ML)
Output limit (MH)
3-position ON/OFF (002)
AUTO or remote (CAS)
Output operation switches
Section
MV open direction
disabled
Manual
AUTO or MAN
4-7
299