Omron CX-PROCESS TOOL V5.2 - 12-2009 Operation Manual page 40

Table of Contents

Advertisement

Relationship with CX-Process Monitor
Generate CX-Process
Monitor Plus Tag File.
Download Function
Block Data to Loop
Controller.
Compile the Monitor Tag
Files.
Setting Initial Data ITEMs
Data
Type
classification
Initial settings
S
Operation data
O
12
• To monitor and set individual contact signals, contact signals must be
input/output using the Contact Distributor block (Block Model 201)
and Internal Switch block (Block Model 209).
• To monitor individual analog signals, analog signals must be output
from the Input Selection block (Block Model 162).
• To set individual analog signals, analog signals must be input to the
Constant Generator block (Block Model 166).
Generate the CX-Process Plus tag file using Execute – Create Tag File – Moni-
tor Plus Tag.
Download the function blocks.
Start the CX-Process Monitor Plus and click the Start Button or the Setup But-
ton. The monitor tag files (mtagmst and mtagsubmst) will be automatically gen-
erated based on the CX-Process Monitor Plus tag file (monitor.csv).
The CX-Process Tool is normally used to set initial data S and the CX-Process
Monitor is normally used to set operation data O.
ITEM
Initial setting parameter
for each function block
Operation parameters
for each function block
Note Initial settings S and operation data O classifications are displayed on ITEM Set-
ting Screens of the CX-Protocol Tool. For details on the ITEMs set in each func-
tion block, refer to the Function Block Reference Manual.
Example
ITEM type
ITEM
Parameter
004
Parameter
008
012
Parameter
023
024
Note Analog values are normally set with the CX-Process Monitor. They can be set
with the CX-Process Tool provided that they are in percentage increments be-
tween 0% and 100%. Scaling engineering units cannot be set with the CX-Pro-
cess Tool.
Example: PID Block
Forward/Reverse direction,
SP setting method,
compensation method, etc.
Example: PID Block SP,
alarm settings, PID
constants, etc.
Contents
Operation cycle (s)
High/Low alarm
Hysteresis set value
Local SP set value
SP set method (Initial setting)
0: Local, 1: Remote/Local
Section
1-2
CX-Process
CX-Process
Tool
Monitor
Set
Cannot be
set
Set in special
Set
cases
R: Read, W: Write,
R/W: Read/write,
---: R/W disabled
r, t/w: CX-Process Tool
operation monitor/Operation
monitor read and write
(S): Initial setting,
(O): Operation data
CX-Process
CX-Process
Tool
Monitor
R/W (S)
---
R/W (O)
R/W
R/W (S)
---
R/W (O)
R/W
R/W (S)
R