Other Settings

○Snap shot function
The current indicated value can be set to the output points SP1 to SP3.
In 3 step setting mode, simple setting mode, or function selection mode, select [SP#] for the display of the
sub display (left). While the sub display (right) is flashing, press the UP and DOWN buttons simultaneously
for 1 second or longer. The set value on the sub display (right) is shown as [- - -], and when the buttons are
released, the same value as the current indicated value is automatically set.
After the setting, readjustment is possible by pressing the UP or DOWN button.
○Differential display function
A differential between each of the set output points (SP1 to SP3) and the current indicated value can be displayed.
Press the UP or DOWN button in measurement mode to switch the sub display (left) as shown below.
While displaying the current value on the main display, the difference with each of the output points (dSP1 to
dSP3) can be displayed at the same time.
Item
dSP1
(Indicated value) - (SP1 set value)
dSP2
(Indicated value) - (SP2 set value)
dSP3
(Indicated value) - (SP3 set value)
: If "SP#" has not been set or the current value is outside the displayable range (HHH or LLL), "dSP#" is shown as "----".
: If the differential displayable range is exceeded, the differential display will be "HH" or "LL".
○Peak or bottom value indication function
The maximum (minimum) voltage at the power on state is detected and updated. In peak/bottom value
display mode, the relevant value is displayed.
Press the Up or DOWN button in measurement mode to switch the sub display (left) as shown below.
The current value on the main display and the peak or bottom value can be displayed on the sub display
(right) at the same time.
The peak or bottom value is maintained even if the power supply is cut off.
When the SET and DOWN buttons are pressed and held for 1 second or longer simultaneously while the
peak or bottom value is displayed, the sub display (right) displays [- - -] and the maximum (minimum)
pressure value is cleared.
Descriptions
-59-
Displayable range
-1999 to 1999
Only in 3 setting mode