Display Sensor Monitor Overview
By using the analogue ASW and the sensor monitor in combination, the switch output can be obtained
according to the analogue value. An analogue ASW can be used without an analogue input card, etc.
When the analogue ASW and the sensor monitor are connected, the output voltage of the analogue ASW is
displayed on the sensor monitor.
By operating the sensor monitor, it is possible to configure settings so that the switch output can be displayed
according to any analogue value.
When output points (SP1 to SP3) are set as voltage values on the sensor monitor, the ON width and the
hysteresis are set before and after each of the output points.
The ON width and the hysteresis can be changed for each of SP1 to SP3.
The chattering of switch output can be prevented by setting a hysteresis.
<Setting example>
Output point (SP1): 2846 [mV]
ON width (W_1): 50 [mV]
Hysteresis (H_1): 20 [mV]
: The ON width plus the hysteresis range is defined as the operating range.
-25-
No.D-※S-OMA1021