DOUT Type options and examples

For all settings of DOUT Type except Latched, the DOUT Type parameter controls the relationship
between the discrete output's On period and Off period.
The following sections provide information on how the duration of the cycle, On period, and Off
period are determined, and examples of DO configuration. In these discussions, one On period plus
one Off period equals one cycle.
7.8.1

Accuracy of Time Duration and TDO Toggle

The DO state calculation is updated at one-second intervals. The calculated On period is then rounded
to the nearest second to produce the actual On period, for example:
Calculated On period = 4.4 seconds; actual On period = 4 seconds
Calculated On period = 4.5 seconds; actual On period = 5 seconds
7.8.2

Durations

DOUT Type = Toggle
Cycle = Time On parameter setting x 2
On period = Off period = Time On parameter setting
DOUT Type = Time Duration
Cycle = Cycle Time setting
On period = Calculated from the current EU value of the assigned process variable
Minimum Off period = Cycle Time minus On period
DOUT Type = TDO Toggle
Cycle = Cycle Time setting
On period = Calculated from the current EU value of the assigned process variable
Off period = Cycle Time minus On period
7.8.3

Examples

A discrete output is used to emulate a field instrument that measures flow. The DO is configured as
follows:
DOUT Type = Time duration
Cycle Time = 12
0% Count = 3
100% Count = 12
Low Reading EU = 0
High Reading EU = 1000
Units = MCF (million cubic feet per day)
78
®