Points and the TLP System
C.3.3

Parameters

Each point type is associated with a unique set of parameters. For a listing of the parameters available
for each standard point type, see the ROC Protocol User Manual.
The parameters associated with the three UDPs are listed below. Note that for UDP 39, parameters
0–50 are displayed in the Select TLP dialog box, but are not used, and are not documented here.
Table C-1
UDP 22 parameters
Read/
Parameter
Write
0
R/W
1
R/O
2
R/O
3
R/W
4
R/W
5
R/O
6
R/W
7
R/W
8
R/W
9
R/W
10
R/O
11
R/O
12
R/O
13
R/O
14
R/O
15
R/O
16
R/O
17
R/O
Table C-2
UDP 37 parameters
Read/
Parameter
Write
0
R/O
1
R/W
2
R/O
3
R/O
4
R/O
Configuration and Use Manual
Data
type
Length
Range
UINT8
1
0 , 1
FL
4
NA
FL
4
NA
FL
4
NA
FL
4
NA
FL
4
NA
T_L_P
3
NA
T_L_P
3
NA
UINT8
1
0 , 1
T_L_P
3
NA
FL
4
NA
FL
4
NA
FL
4
NA
FL
4
NA
STRNG20 20
NA
FL
4
NA
FL
4
NA
FL
4
NA
Data
type
Length
Range
FL
4
NA
INT16
2
0 – 4
UINT16
2
0 – 65535
UINT8
1
1 – 16
FL
4
NA
Default
value
Description
1
Mass Pressure Correction Enable Flag
• 0 = Disabled
• 1 = Enabled
0.0
Mass Flow Rate from Sensor
0.0
Pressure Corrected Mass Flow Rate
–0.0008
Pressure Effect for Mass Correction
(Peffct)
30.0
Cal Pressure for Mass Correction (Pcal)
0.0
Volume Rate at Flowing Conditions
47,0,25
Base Density Input Definition
47,0,24
Flowing Density Input Definition
1
Analog Output Write Enable
47,0,0
Source Definition for Analog Output
Value
0.0
Value Written to Analog Output
0.0
Density Value from Sensor
0.0
Density Value from Base Density Input
0.0
Density Value from Flowing Density
Input
"
" Density Properties Calculation
Description
0.0
Calculation Period (in seconds)
0.0
Mass Pressure Compensation Factor
0.0
Flowing Pressure Value in PSI
Default
value
Description
0.0
Live Data Polling Period
0
Polling State
• 0 = Polling Live Data
• 1 = Reading Setup Data
• 2 = Writing Setup Data
• 4 = Response Timeout
245
Live Data Register 1 (Sensor Status)
FL (7)
Live Data Register 1 Data Type
0.0
Live Data Register 1 Value
205