Calibration
Figure B-3
2. In the Point dropdown list, select the point number of the AI or RTD whose calibration values
you want to view. The Tag displays the name of the selected point.
3. Parameters in the AI Calibration Values dialog box are listed and defined in Table B-1.
Table B-1
AI Calibration Values parameters
Parameter
Description
Raw Value
Displays the calibrated Raw A/D input.
#1 to 5
• #1 is the lowest value.
• #5 is the highest value.
EU Value
Displays the values entered during calibration.
#1 to 5
Press Effect
Not applicable to the Model 3711.
Set EU Value
Displays the Tester value specified for the last calibration value
that was set.
Manual EU
Displays the Live Reading value for the last calibration value
that was set.
Timer
Not applicable to the Model 3711.
Mode
Not applicable to the Model 3711.
Type
Not applicable to the Model 3711.
198
AI Calibration Values dialog box
Comments
Displayed in EUs, converted from
the raw values based on the Low
Reading EU and High Reading EU
defined for the point.
®
Micro Motion
Model 3711 Gas Flow Computers