Modbus Interface
Table 12-1
Modbus Configuration – General parameters
Parameter
Description
Status
Displays the Model 3711 Modbus slave status.
Modbus Type
• ASCII: 7-bit communications
• RTU: 8-bit communications
Log Modbus
• Disabled: Parameter changes made via Modbus
Events
communications are not logged.
• Enabled: Parameter changes made via Modbus
communications are logged.
Byte Order
• LSB: The least significant byte is sent first
• MSB: The most significant byte is sent first
EFM Modbus
• Disabled: Standard formats are applied to date and time
values in history data, event and alarm logs, and the
configured date and time registers.
• Enabled: EFM formats are applied to date and time values in
the locations listed above.
Date Register
Specify the Modbus register that will be used to store the
real-time date value.
Time Register
Specify the Modbus register that will be used to store the
real-time time value.
3. Open the
136
panel. The panel shown in Figure 12-3 is displayed.
Scale Values
Comments
Possible states:
• OK
• Illegal function
• Illegal data address
• Illegal data value
• Unknown error
Default: RTU
Default: Enabled
Default: LSB
For effects on transmission of
floating-point values, see
Section 12.5.2.
Default: Enabled
See Section 12.5.4 for a definition
of the formats.
Default: 7046.
Default: 7047.
®