Installation Types and Components
The Mass Flow Interface termination board is installed on top of the base termination board (see
Figure A-6).
The Mass Flow Interface termination board provides the PWR+ and PWR– terminals that
power the system, and the MVD terminals for the RS-485 connection to the sensor. The Mass
Flow Interface board is required for Model 3711 operation.
The base termination board, beneath the Mass Flow interface board, provides ground screws,
I/O terminals, etc.
For more information, see the Model 3711 installation manual.
Note: Do not use the MVD+ and MVD– terminals to supply power to the I.S. barrier. Instead, use the
PWR+ and PWR– terminals. For more information, see the Model 3711 installation manual.
Figure A-6
Mass Flow Interface board
MVD terminals for RS-485
connection to sensor
Power wires to I.S. barrier
192
Model 3711 with Mass Flow Interface board
Base termination board
Internal ground
screws
PWR+ and PWR–
terminals
Power wires from external
power supply
®
Micro Motion
Model 3711 Gas Flow Computers