Emerson Micro Motion 3711 Configuration And Use Manual page 77

Gas flow computers
Table of Contents

Advertisement

Configuring I/O
Figure 7-6
Analog Outputs – Advanced panel
Table 7-5
Analog Outputs – Advanced parameters
Parameter
Description
Raw D/A Output
The current value produced by the Digital-to-Analog converter.
Adjusted D/A 0%
The Digital-to-Analog value corresponding to 0% output.
Adjusted D/A
The calibrated Digital-to-Analog reading corresponding to 100%
100%
output.
Value on Power
Specifies the startup value to be used by this AO if a power
Reset
reset or warm start occurs.
RBX Alarming
Specifies the type of Report By Exception alarming for this
output:
• Disabled – No RBX alarming.
• On Alarm Set – RBX alarm generated when the analog output
enters an alarm condition.
• On Alarm Clear – RBX alarm generated when the analog
output leaves an alarm condition.
• On Alarm Set and Clear – RBX alarm generated when the
analog output enters an alarm condition and when the analog
output leaves an alarm condition.
Configuration and Use Manual
Comments
Read-only.
Used in conversion of EUs to an
analog signal.
Adjust this value as required for
agreement between the
Model 3711 and the remote
device. See Section B.3.
Used in conversion of EUs to an
analog signal.
Adjust this value as required for
agreement between the
Model 3711 and the remote
device. See Section B.3.
• Low EU: The Low EU value is
used to calculate the startup AO
signal.
• Retain Last Value: The last EU
value before the power reset is
used to calculate the startup AO
signal.
If RBX Alarming is enabled, a
communications port must be
configured for RBX alarming. See
.
Section 4.6