Summary: This procedure provides instructions for verifying the source 48 Vdc power supply.
1. Turn on the power source that will supply power to the system.
2. Use a multi-tester to measure the DC voltage at the source. When testing, place the positive
probe on the 48 V terminal and the negative probe on the COM or RTN terminal.
3. The measured voltage must be between 42.5 Vdc and 56.5 Vdc at the specified point.
Was voltage within range specified? Note the polarity.
If No, proceed to step 4.
If Yes, continue with step 5.
4. The problem is in the power supply wiring or in the 48 Vdc power supply. Isolate the
problem using local troubleshooting practices and correct as required before installing
power to the system. Repeat procedure after correcting problem.
5. Install fuses or engage the circuit breakers that supply power to the shelf. The front access
cards should illuminate. This can be verified by observing the shelf alarm indicator on the
front door panel. This will only light up if the SC cards are installed and an alarm is
present. Refer to Figure 700-1.
Stop! You have completed this procedure.
SHELF
ALARM
INDICATOR
DOOR
HINGES
LOWER AIR INTAKE/
CABLE ROUTING TRAY
1152700 Issue 1 February 2001 Section 2 Operations and Maintenance

POWER UP A CELLWORX STN NODE

Figure 700-1. Cellworx STN Component Identification
DLP-700
Page 1 of 1
UPPER HEAT BAFFLE/
FIBER MANAGEMENT TRAY
ESD GROUND JACK
DOOR
LATCH
10479-C
Page 2-45
© 2000, ADC Telecommunications, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cellworx stn

Table of Contents