LOGO! installation and wiring
2.3 Wiring LOGO!
2.3.8

Connecting the Ethernet interface (0BA7 only)

LOGO! ...E
The LOGO! ...E version is equipped with a 10/100 Mbit/s Ethernet RJ45 interface.
Requirements for the network cable
You can connect a standard Ethernet cable to the Ethernet interface. To minimize
electromagnetic interference, however, Siemens recommends you use a standard Category
5 shielded twisted-pair Ethernet cable with a shielded RJ45 connector on each end.
Connecting
You connect the PE terminal to earth ground, and connect a network cable to the Ethernet
interface.
Ethernet status LEDs
LED
Rx/Tx
LINK
62
Earth ground
Ethernet cable, for connecting to the Ethernet interface
Ethernet status LEDs
Color
Flashing orange
Steady green
Description
LOGO! is receiving/sending data across Ethernet
LOGO! is already connected to Ethernet
Manual, 04/2011, A5E03556174-01