Delay time at 0 to 1:
•
•
•
•
Delay time at 1 to 0:
•
•
•
•
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
In groups of
Control of a digital input
Continuous current I
Surge current
Incandescent lamp load (25000
switching cycles) at:
230/240 V AC
115/120 V AC
Fluorescent tubes with ballast
(25000 switching cycles)
Fluorescent tubes,
conventionally compensated
(25000 switching cycles)
Fluorescent tubes,
uncompensated (25000
switching cycles)
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Derating
Parallel output circuits for power
increase
Protection of output relay (if
desired)
Switching rate
Mechanical
Ohmic load/lamp load
Inductive load
LOGO!
Manual, 04/2011, A5E03556174-01
120V AC
240 V AC
120 V DC
240V DC
120V AC
240 V AC
120 V DC
240V DC
th
A.3 Technical data: LOGO! DM8 230R and LOGO! DM16 230R
LOGO! DM8 230R
typ. 50 ms
•
typ. 30 ms
•
typ. 25 ms
•
typ. 15 ms
•
typ. 65 ms
•
typ. 105 ms
•
typ. 95 ms
•
typ. 125 ms
•
max. 100 m
4
Relay outputs
Yes
1
Yes
max. 5 A per relay
max. 30 A
1000 W
500 W
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire
temperature range
Not permitted
max. 16 A,
characteristic B16
10 Hz
2 Hz
0.5 Hz
Technical data
LOGO! DM16 230R
typ. 50 ms
•
typ. 30 ms
•
typ. 25 ms
•
typ. 15 ms
•
typ. 65 ms
•
typ. 105 ms
•
typ. 95 ms
•
typ. 125 ms
•
max. 100 m
8
Relay outputs
Yes
1
Yes
max. 5 A per relay
max. 30 A
1000 W
500 W
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire
temperature range
Not permitted
max. 16 A,
characteristic B16
10 Hz
2 Hz
0.5 Hz
325