Siemens LOGO! Series Manual page 325

Hide thumbs Also See for LOGO! Series:
Table of Contents

Advertisement

Delay time at 0 to 1:
Delay time at 1 to 0:
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
In groups of
Control of a digital input
Continuous current I
Surge current
Incandescent lamp load (25000
switching cycles) at:
230/240 V AC
115/120 V AC
Fluorescent tubes with ballast
(25000 switching cycles)
Fluorescent tubes,
conventionally compensated
(25000 switching cycles)
Fluorescent tubes,
uncompensated (25000
switching cycles)
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Derating
Parallel output circuits for power
increase
Protection of output relay (if
desired)
Switching rate
Mechanical
Ohmic load/lamp load
Inductive load
LOGO!
Manual, 04/2011, A5E03556174-01
120V AC
240 V AC
120 V DC
240V DC
120V AC
240 V AC
120 V DC
240V DC
th
A.3 Technical data: LOGO! DM8 230R and LOGO! DM16 230R
LOGO! DM8 230R
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
max. 100 m
4
Relay outputs
Yes
1
Yes
max. 5 A per relay
max. 30 A
1000 W
500 W
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire
temperature range
Not permitted
max. 16 A,
characteristic B16
10 Hz
2 Hz
0.5 Hz
Technical data
LOGO! DM16 230R
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
max. 100 m
8
Relay outputs
Yes
1
Yes
max. 5 A per relay
max. 30 A
1000 W
500 W
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire
temperature range
Not permitted
max. 16 A,
characteristic B16
10 Hz
2 Hz
0.5 Hz
325