Technical data
A.1 General technical data
Ambient mechanical conditions
Degree of protection
Vibrations:
Shock
Free fall (packaged)
Electromagnetic compatibility (EMC)
Noise emission
Electrostatic discharge
Electromagnetic fields
HF currents on cables and cable
shielding
Burst pulses
High-energy surge pulse (applies only
to LOGO! 230 ...)
Safety to IEC
Clearance and creepage distance
rating
Insulation strength
Cycle time
Cycle time per function
Startup
Startup time at power-up
320
Criterion
Tested in accordance with
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-32
EN 55011/A
EN 55022/B
EN 50081-1
(domestic area)
IEC 61000-4-2
Severity 3
IEC 61000-4-3
IEC 61000-4-6
IEC 61000-4-4Severity 3
IEC 61000-4-5Severity 3
IEC 60664, IEC 61131-2,
EN 50178
cULus to UL 508, CSA
C22.2 No. 142
With LOGO! 230 R/RC,
also IEC60730-1
IEC 61131-2
Values
IP 20 for LOGO! Base Modules,
expansion modules, and the
LOGO! TD excluding the TD
front panel
IP 65 for LOGO! TD front panel
5 ... 8.4 Hz
(constant amplitude 3.5 mm)
8.4 ... 150 Hz
(constant acceleration 1 g)
18 shocks
(half-sine wave 15g/11 ms)
0.3 m
Limit class B group 1
8 kV air discharge
6 kV contact discharge
Field strength 1 V/m and 10
V/m
10 V
2 kV (supply and signal lines)
1 kV (power lines) symmetrical
2 kV (power lines) asymmetrical
Fulfilled
Fulfilled
< 0.1 ms
typ. 9 s