LOGO! functions
4.4 Special functions list - SF
4.4.36
Average value (0BA7 only)
Short description
The average value function calculates the average value of an analog input over a
configured time period.
Symbol in LOGO!
* AI1...AI8: 0...10 V corresponds with 0...1000 (internal value).
276
Wiring
Description
En
A change in status from 0 to 1 transition at input En
starts the average value function.
A change in status from 1 to 0 at input En holds the
analog output value.
R
A signal at input R clears the analog output value.
Ax
Input Ax is one of the following analog signals:
Parameter
St (Sampling time): You can set the timebase to s
(seconds), d (days), h (hours), or m (minutes).
Range of values:
St = s: 1 to 59
St = d: 1 to 365
St = h: 1 to 23
St = m: 1 to 59
Sn (Number of samples):
Range of values:
St = s: 1 to St*100
St = d: 1 to 32767
St = h: 1 to 32767
St = m and St ≤ 5 minutes: 1 to St*6000
St = m and St ≥ 6 minutes: 1 to 32767
Retentivity:
/ = No retentivity
R = Retentivity
Output AQ
Outputs the average value of input Ax over
configured time sampling period.
AI1 to AI8 (*)
AM1 to AM16
NAI1 to NAI32
AQ1 to AQ2
NAQ1 to NAQ16
Block number of a function with analog output