Timing diagram (example)
Functional description
ERst = 1 and En = 0: The function sets the AQ value to 0.
ERst = 1 and En = 1: The function outputs a value at AQ, depending on the settings of Mode
and S1.
ERst = 0 and En = 0: The function holds the value of AQ at the current value.
ERst = 0 and En = 1: The function outputs a value at AQ, depending on the settings of Mode
and S1.
Mode = 0: The function sets AQ to the minimum value
Mode = 1: The function sets AQ to the maximum value
Mode = 2 and S1 = 0: The function sets AQ to the minimum value
Mode = 2 and S1 = 1: The function sets AQ to the maximum value
Mode = 3: The function outputs current analog input value.
Setting the Par parameter
View in programming mode (example)
LOGO!
Manual, 04/2011, A5E03556174-01
LOGO! functions
4.4 Special functions list - SF
275