Technical Data: Logo! Am2 Aq - Siemens LOGO! Series Manual

Hide thumbs Also See for LOGO! Series:
Table of Contents

Advertisement

Cable length (shielded)
Interference frequency
suppression
A.13

Technical data: LOGO! AM2 AQ

Power supply
Input voltage
Permissible range
Power consumption
Voltage failure buffering
Power loss at 24 V
Electrical isolation
Reverse polarity protection
Ground terminal
Analog outputs
Number
Voltage range
Voltage load
Current output
Curreny load
Resolution
Cycle time for analog output
Electrical isolation
Line length (shielded and twisted)
Error limit
Short circuit protection
Overload protection
Note
The 0/4 ... 20 mA current output is only possible when the module is used with a LOGO!
0BA6 or LOGO! 0BA7 Base Module.
LOGO!
Manual, 04/2011, A5E03556174-01
A.13 Technical data: LOGO! AM2 AQ
LOGO! AM2 RTD
max. 10 m
55 Hz
LOGO! AM2 AQ
24 V DC
20.4 ... 28.8 V DC
35 ...90 mA
typ. 5 ms
0.9 ... 2.2 W
No
Yes
for connecting ground and shielding of the analog
output line.
2
0 ... 10 V DC
≥5 kΩ
0/4...20mA
≤250 Ω
10 bit, normalized to 0 ... 1000
depending on installation (50 ms)
No
max. 10 m
Voltage output: ± 2.5 % FS
Voltage output: Yes (affect neighboring voltage output)
Voltage output: Yes (affect neighboring voltage output)
Technical data
341