Operating
8.5 Simulation
A simulated value (from a preset selection, or a value set by customer) can be set to test the
functioning of the mA connections during commissioning or maintenance of the device. The
range is 3.55 mA to 22.8 mA.
Note
Simulated current output
The simulated current output value influences output to the control system.
In general, to simulate current output:
1. Run the "Loop test wizard" from the menu "Maintenance and diagnostics > Loop test" on the
device (or from the Device menu in SIMATIC PDM).
– Select a preset mA value, or enter a custom value. (Custom value can be entered by
2. Start the loop test.
3. When you are ready to end the simulation, stop the loop test by exiting the wizard.
The device returns to the actual output value.
8.5.1

Simulation - Process value (Operating chapter)

Process value simulation
Process value simulation is an iterative process whereby parameters are adjusted and
corresponding results are displayed. Process values can be simulated using a remote
90
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
selecting "User" option on device, or "Other" option in PDM.)
Upper saturation limit (factory
setting)
Upper fault current (factory set‐
ting)
 
 
SITRANS LR500 series with mA/HART
Operating Instructions, 03/2024, A5E51099898-AA