20. EMC AND LOW VOLTAGE DIRECTIVES

20.1.1 EMC standards

Standards related to the EMC directives are described below.
Specifications
EN55011
Radiated noise
EN61000-6-4
(2001)
EN55011
Conduction noise
EN61000-4-2
Static electricity immunity
EN61000-4-4
First transient burst noise
EN61131-2/A12
(2000)
EN61000-4-12
Damped oscillatory wave
EN61000-4-3
Radiated electromagnetic field
EN61000-6-2
EN61000-4-6
(2001)
Conduction noise
Test Item
*2
*2
*2
*2
*2
*2
*2
*1
QP: Quasi-peak value, Mean: Average value
*2
The PLC is an open type device (device installed to another device) and must be installed in a
conductive control panel.The tests for the corresponding items were performed while the PLC
was installed inside the control panel.
Test Description
Measure the emission released by
the product.
Measure the emission released by
the product to the power line.
Immunity test by applying static
electricity to the module enclosure.
Immunity test by applying burst
noise to the power line and signal
line.
Immunity test in which damped
oscillatory waves are applied to
power line.
Immunity test in which electric fields
are applied to the product.
Immunity test in which
electromagnetic fields are induced to
power cables and signal line.
20 - 2
Standard Values
30 M-230 M Hz QP :
30dB V/m (30m measurement)
230 M-1000 M Hz QP :
30dB V/m (30m measurement)
150 K-500k Hz QP:
*1
79 dB, Mean : 66 dB
500 K-30M Hz QP :
*1
73 dB, Mean: 60 dB
4kV
contact discharge
8kV
air discharge
2kV
power line
1kV
signal line
1kV
10V/m, 26-1000MHz
10V, 0.15-80MHz
*1
*1