APPENDICES
Special
ACPU
Special
Register
Special
Register for
after
Register
Modification
Conversion
D9009
SD1009
SD62
D9015
SD1015
SD203
D9016
SD1016
D9017
SD1017
SD520
D9018
SD1018
SD524
D9019
SD1019
SD526
Table App. 3.11. Special register
Name
Meaning
F number at which
Annunciator
external failure has
detection
occurred
Operating
Operating status of
status of CPU
CPU
0: Main program
(ROM)
1: Main program
(RAM)
2: Subprogram 1
(RAM)
3: Subprogram 2
(RAM)
4: Subprogram 3
(RAM)
5: Subprogram 1
(ROM)
Program
6: Subprogram 2
number
(ROM)
7: Subprogram 3
(ROM)
8: Main program
2
(E
PROM)
9: Subprogram 1
2
(E
PROM)
A: Subprogram 2
2
(E
PROM)
B: Subprogram 3
2
(E
PROM)
Minimum scan time
Scan time
(10 ms units)
Scan time
Scan time
(10 ms units)
Maximum scan time
Scan time
(10 ms units)
App - 96
Details
• When one of F0 to 2047 is turned on by
, the F number, which has been detected earliest among
SET F
the F numbers which have turned on, is stored in BIN code.
• SD62 can be cleared by
or
RST F
If another F number has been detected, the clearing of SD62
causes the next number to be stored in SD62.
• When one of F0 to 2047 is turned on by
F number, which has been detected earliest among the F numbers
which have turned on, is stored in BIN code.
• SD62 can be cleared by executing
instruction or moving INDICATOR RESET switch on CPU module
front to ON position.
If another F number has been detected, clearing of SD62 stores
the next F number into SD62.
• The operation status of CPU as shown below are stored in SD203.
b15
to
b12
b11
to
b8
b7
to
Remote RUN/STOP
by computer
0
RUN
1
STOP
2
PAUSE
1
Status in program
0
Except below
STOP
1
Instruction
execution
*1:
When the CPU mdoule is in RUN mode and SM1040 is off, the
CPU module remains in RUN mode if changed to PAUSE
mode.
• Indicates which sequence program is run presently. One value of 0
to B is stored in BIN code.
• If scan time is smaller than the content of SD520, the value is
newly stored at each END. Namely, the minimum value of scan
time is stored into SD520 in BIN code.
• At every END, the scan time is stored in BIN code and always
rewritten.
• If scan time is larger than the content of SD526, the value is newly
stored at each END. Namely, the maximum value of scan time is
stored into SD526 in BIN code.
Corresponding
or
OUT F
instruction.
LEDR
or
, the
OUT F
SET F
or
LEDR
RST F
b4
b3
to
b0
CPU key switch
0
RUN
1
STOP
2
PAUSE
1
3
STEP RUN
Remains the same in
remote RUN/STOP
mode.
Remote RUN/STOP
by parameter setting
0
RUN
1
STOP
2
PAUSE
1
CPU
Q2AS
Q2A
Q3A
Q4A
Q4AR
QnA
QnA
QnA
QnA
QnA