Mitsubishi Q2ACPU User Manual page 106

Qna series melsec
Table of Contents

Advertisement

8.
DEBUGGING FUNCTION
(3)
GPPQ Model Name
SW0 -GPPQ
SW1 -GPPQ
When local
device is not
set
SW2 -GPPQ
When local
device is set
REMARK
(4)
Operation for CPU module and GPP function versions
Table 8.1 shows the operation when the local devices are set to D0 to D99 and when
3 programs with the program names of "A", "B" and "C" are performed in the CPU
module.
(The order of the programs is A, B, C, (END processing), A, B...)
Table 8.1 Operation for CPU module and GPPQ function versions
With Function Version "B"
D0
D0 of program "C" is
monitored.
D0 of program "C" is
monitored.
D0 of the displayed
program is set.
GX Developer supports functions of function version B.
Precautions
(a) The local device that can perform the monitor test in one peripheral device is
only one program.
Monitor test for multiple program local devices from one peripheral device is not
allowed.
(b) The number of programs that allows simultaneous monitor test from multiple
peripheral devices is up to 16.
When the local device of the stand-by type program is monitored, the local
device data is read/escape. The scan time is extended as follows:
Q2ACPU(S1)
Q3ACPU
Q4ACPU
Monitor Device
D100
D100 after execution of
D0 of program "C" is
program "C" is
monitored.
monitored.
D100 after execution of
D0 of program "C" is
program "C" is
monitored.
monitored.
D100 after execution of
the displayed program is
An error (error code: 4001) occurs.
set.
:560 + 1.3 (Number of words in the local device) [ s]
:425 + 1.0 (Number of words in the local device) [ s]
:220 + 0.8 (Number of words in the local device) [ s]
8 - 14
Without Function Version "B"
D0
D100
D100 after execution of
program "C" is
monitored.
D100 after execution of
program "C" is
monitored.