Standards Relevant To The Emc Directive - Mitsubishi Q01CPU User Manual

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

9
EMC AND LOW VOLTAGE DIRECTIVES

9.1.1 Standards relevant to the EMC Directive

The standards relevant to the EMC Directive are listed in Table9.1.
Specification
EN61000-4-2
Electrostatic discharge
immunity
EN61000-4-3
Radiated electromagnetic
field immunity
EN61000-4-4
Electrical fast transient/
burst immunity
EN61131-2:
2003
EN61000-4-5
Surge immunity
EN61000-4-6
Conducted disturbances
immunity
*1:
QP : Quasi-peak value, Mean : Average value
*2:
Programmable controller is an open type device (a device designed to be housed inside other equipment) and must be
installed inside a conductive control panel.
The corresponding test has been conducted with the programmable controller installed inside a control panel.
Besides, our programmable controller has been tested with the maximum rated input value of the power supply module
to be used.
9
- 2
9.1 Requirements for Conformance to EMC Directive
9.1.1 Standards relevant to the EMC Directive
Table9.1 Standards relevant to the EMC Directive
Test item
Immunity test in which
electrostatic is applied
*2
to the cabinet of the equipment.
Immunity test in which electric
fields are irradiated to the
*2
product.
Immunity test in which burst
noise is applied to the power
*2
cable and signal line.
Immunity test in which burst
noise is applied to the power line
*2
and signal line.
Immunity test in which high
frequency noise is applied to the
*2
power line and signal line.
Test details
8kV Air discharge
4kV Contact discharge
1.4GHz-2.0GHz, 80-1000MHz, 10V/m,
80%AM modulation@1kHz
AC power cable:
DC power cable:
I/O power(DC):
DC I/O, analog, communication
line(shielded):
AC power line:
Common mode
mode
DC power line:
Common mode
mode
I/O power(DC):
Common mode
mode
DC I/O, analog, communication (shielded):
Common mode
0.15-80MHz, 80%AM modulation 1kHz,
3Vrms
Standard value
2kV
2kV
1kV
1kV
2kV, differential
1kV
1kV, differential
0.5kV
0.5kV, differential
0.5kV
1kV