Preparations
Always check the following before you execute autotuning without a host reference.
• The main circuit power supply must be ON.
• There must be no overtravel.
• The servo must be OFF.
• The gain switching selection must be set to disable automatic gain switching (Pn139 =
n.0).
• The first gains must be selected.
• The test without a motor function must be disabled (Pn00C = n.0).
• There must be no alarms or warnings.
• There must be no hard wire base block (HWBB).
• The parameters must not be write prohibited.
• The tuning-less function must be disabled (Pn170 = n.0), or the tuning-less function
must be enabled (Pn170 = n.1) and moment of inertia estimation must be specified.
• If you execute autotuning without a host reference during speed control, set the mode to 1.
• If you start autotuning without a host reference while the SERVOPACK is in speed control
Information
8.6.3

Applicable Tools

The following table lists the tools that you can use to perform autotuning without a host refer-
ence and the applicable tool functions.
Tool
Digital Operator
SigmaWin+
8.6.4

Operating Procedure

Use the following procedure to perform autotuning without a host reference.
 If you specify not estimating the moment of inertia, set the moment of inertia ratio (Pn103)
correctly. If the setting greatly differs from the actual moment of inertia ratio, normal control
of the machine may not be possible, and vibration may result.
1.
Confirm that the moment of inertia ratio (Pn103) is set correctly.
2.
Select Tuning - Tuning from the menu bar of the Main Window of the SigmaWin+.
The Tuning Dialog Box will be displayed.
Click the Cancel Button to cancel tuning.
for mode 2 or 3, the SERVOPACK will change to position control automatically to perform
autotuning without a host reference. The SERVOPACK will return to speed control after
autotuning has been completed.
Function
Fn201
Tuning - Tuning
8.6 Autotuning without Host Reference
Operating Procedure Reference
Σ-7-Series Digital Operator Operating
Manual (Manual No.: SIEP S800001 33)
8.6.4 Operating Procedure on page 8-25
CAUTION

8.6.3 Applicable Tools

8-25