9.2.3

I/O Signal Monitor

Use the following procedure to check I/O signals.
1.
Select Monitor - Check Wiring from the menu bar of the Main Window of the Sig-
maWin+.
2.
Click the Monitor Mode Button.
You can also use the above window to check wiring.
Information
• Checking Input Signal Wiring
• Checking Output Signal Wiring
Input signal status
Change the signal status at the host controller. If the input signal status on the window
changes accordingly, then the wiring is correct.
Click the Force Output Mode Button. This will force the output signal status to change. If
the signal status at the host controller changes accordingly, then the wiring is correct.
You cannot use the Force Output Mode Button while the servo is ON.
9.2 Monitoring SERVOPACK Status
Output signal status

9.2.3 I/O Signal Monitor