Advertisement

1. If the same alarm occurs consecutively within one hour, it is not saved in the alarm history.
Information
2. You can clear the alarm history by clicking the Clear Button. The alarm history is not
This concludes the procedure to display the alarm history.
14.2.5

Clearing the Alarm History

You can clear the alarm history that is recorded in the SERVOPACK.
The alarm history is not cleared when alarms are reset or when the SERVOPACK main circuit
power is turned OFF. You must perform the following procedure.
Preparations
Always check the following before you clear the alarm history.
• The parameters must not be write prohibited.
Applicable Tools
The following table lists the tools that you can use to clear the alarm history and the applicable
tool functions.
Tool
Digital Operator
SigmaWin+
Operating Procedure
Use the following procedure to reset the alarm history.
1.
Select Alarm - Display Alarm from the menu bar of the Main Window of the SigmaWin+.
The Alarm Display Dialog Box will be displayed.
2.
Click the Alarm History Tab.
3.
Click the Clear Button.
The alarm history will be cleared.
This concludes the procedure to reset the alarm history.
If it occurs after an hour or more, it is saved.
cleared when alarms are reset or when the SERVOPACK main circuit power is turned OFF.
Function
Fn006
Alarm − Display Alarm
14.2 Alarm Displays

14.2.5 Clearing the Alarm History

Reference
Σ
-7-Series Digital Operator Operating Manual
(Manual No.: SIEP S800001 33)
Operating Procedure on page 14-43